Ürün Açıklaması
FieldConnex® FieldBarrier®
General specifications
Design / MountingCabinet installation
Fieldbus connection
Power dissipationsee table 1
Main cable (Trunk)
Rated voltage16 … 32 V DC ,
min. 15 V in case of brown out
Rated currenttrunk IN to trunk OUT max. 2 A see table 1
Cable shield grounding optionCapacitive via 5.7 nF
Direct
Voltage droptrunk IN to trunk OUT 100 mV max.
Number of couplersmax. 3 per segment
Reverse polarity protectionBuilt-In
Outputs
Number of outputs8, 10 or 12
Number of devices per output1
Cable length120 m
Rated voltage10 … 14 V
Rated currentmax. 43 mA at one spur ,
max. 320 mA total current at all spurs
Short-circuit current53 mA , 1 mA in fallback state
Cable shield grounding optionCapacitive via 4.4 nF
Surge protectionTrunk overvoltage protection if voltage exceeds typ. 39 V, max. 41 V
Diagnostic and Protection Features
Fault IsolationShort Circuit Current Limitation at spurs
Bounce Protection at spurs
Signal inhibit at spurs
Physical Layer DiagnosticSignal level at spurs
Signal jitter at spurs
Noise level at spurs
Indicators/operating means
SwitchS1 ON: diagnostic alarms activated
S2 ON: diagnostic warnings activated
S3-S8: not used
LED PWRgreen: Fieldbus voltage > 16 V
LED COM/ERRyellow flashing: fieldbus communication and physical layer status ,
red: Hardware error
LED SPURSred: 2 Hz flashing in short-circuit condition
Galvanic isolation
Main wire/outputsisolation is not affected by interference according to EN 60079-11, voltage peak value 375 V
Output/OutputNo Isolation
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013
Standard conformity
Electromagnetic compatibilityNE 21:2011
Degree of protectionIEC/EN 60529
Fieldbus standardIEC 61158-2
Climatic conditionsIEC 60721
Shock resistanceEN 60068-2-27
Vibration resistanceEN 60068-2-6
Ambient conditions
Ambient temperature-40 … 70 °C (-40 … 158 °F)
Storage temperature-40 … 85 °C (-40 … 185 °F)
Relative humidity< 95 % non-condensing
Shock resistance15 g 11 ms
Vibration resistance1 g , 10 ... 150 Hz
Corrosion resistanceacc. to ISA-S71.04-1985, severity level G3Mechanical specificationsConnection typepluggable , screw terminal or spring terminal
Core cross sectionsee table 2
Housing materialPolycarbonate
Degree of protectionIP20 ,
IP30 for Ex-e terminal cover
Mass2100 g
Dimensionssee dimensions
MountingDIN rail mounting and wall mountingData for application in connection with hazardous areasEU-type examination certificateBVS 13 ATEX E 121 X
Marking II 2(1)G Ex eb ib mb [ia Ga] IIC T4 Gb
II (1)D [Ex ia Da] IIIC
I (M1) [Ex ia Ma] I
Main cable (Trunk)
Maximum safe voltageUm253 V AC
Outputsin accordance to FISCO and Entity
Power1.063 W
Voltage17.1 V
Current248.55 mA
Inductancegas group IIC 470 µH ,
gas group IIB 2 mH
Capacitancegas group IIC 367 nF ,
gas group IIB 2.15 µF
Directive conformity
Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012 , EN 60079-18:2015International approvalsCSA approvalCSA 14.70004139
Control drawing116-0400
Approved forClass I, Division 2, Groups A, B, C, D T4
Class I, Zone 1, AEx/Ex e ib mb [ia Ga] IIC T4 Gb
Class I, Zone 1, AEx/Ex e ib mb [ia IIC Da] IIC T4 Gb
Associated equipment for Class I, Division 1 Groups A, B, C, D
Associated equipment for Class II, Division 1 Groups E, F, G
Associated equipment for Class III, Division 1
IECEx approvalIECEx BVS 13.0119X
Approved forEx eb ib mb [ia Ga] IIC T4 Gb
[Ex ia Da] IIIC
[Ex ia Ma] ICertificates and approvalsFOUNDATION FieldbusFF-846General informationSupplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.