Ürün Açıklaması
Kabin Montajı İçin Segment Koruyucu
General specifications
Design / MountingCabinet installation
Fieldbus connection
Power dissipation250 mW
Main cable (Trunk)
Rated voltage9 … 32 V DC
Outputs
Number of outputs12
Rated voltagemax. 32 V
Rated currentmax. 40 mA
Short-circuit currentmax. 52 mA
Self current consumptionmax. 9 mA
Voltage drop main cable/outputsmax. 1.3 V
Terminating resistorselectable 100 Ω integrated
Surge protectiontrunk, spurs overvoltage protected if voltage exceeds typ. 39 V, max. 41 V
Indicators/operating means
LED PWRgreen: Fieldbus voltage > 10 V
LED CHANNEL ERRORred flashing: short-circuit
LED COMyellow: bus activity
LED TERM ONyellow: termination activated
Directive conformity
Electromagnetic compatibility
Directive 2004/108/ECEN 61326-1:2006
Standard conformity
Electromagnetic compatibilityNE 21:2006
Degree of protectionIEC 60529
Fieldbus standardIEC 61158-2
Shock resistanceEN 60068-2-27
Vibration resistanceEN 60068-2-6
Ambient conditions
Ambient temperature-40 … 70 °C (-40 … 158 °F)
Storage temperature-40 … 85 °C (-40 … 185 °F)
Relative humidity95 % non-condensing
Shock resistance15 g , 11 ms
Vibration resistance5 g , 10 … 150 Hz
Mechanical specifications
Connection typescrew fixing
Core cross sectionmax. 2.5 mm2 / AWG 12-24
Housing materialPolycarbonate
Housing width216 mm
Housing height100 mm
Housing depth50 mm
Degree of protectionIP20
Mass800 g
MountingDIN rail mounting
Coatingresin filled
Data for application in connection with hazardous areas
EU-type examination certificatePTB 04 ATEX 2100 X
Marking II 2 G Ex e mb IIC T4 Gb
Maximum values
Rated voltage≤ 35 V
Prospective short-circuit current100 A
Directive conformity
Directive 94/9/ECEN 60079-0:2012 , EN 60079-7:2007 , EN 60079-18:2009
International approvals
IECEx approvalIECEx PTB 05.0010X
Approved forEx me II T4
Certificates and approvals
Marine approvalDNV A-14038
General information
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.