Ürün açıklaması
Ultrasonik doğrudan algılama sensörü
General specifications
Sensing range40 … 400 mm
Dead band0 … 40 mm
Standard target plate20 mm x 20 mm
Transducer frequencyapprox. 300 kHz
Response delay≤ 75 ms
Limit data
Permissible cable lengthmax. 300 m
Indicators/operating means
LED yellowobject inside the scanning range
Electrical specifications
Rated operating voltage24 V DC
Operating voltage20 … 30 V DC , ripple 10 %SS ; 12 … 20 V DC sensitivity reduced to 90 %
No-load supply current≤ 20 mA
Time delay before availability≤ 150 ms
Input
Input type1 program input
Levellow level : 0 … 0.7 V (Teach-In active)
high level : UB or open input (Teach-In inactive)
Input impedance16 kΩ
Pulse length≥ 3 s
Output
Output typeFrequency output , PNP
Rated operating current100 mA , short-circuit/overload protected
Voltage drop≤ 2 V
ResolutionStandard: 2 Hz / mm , low: 1 Hz / mm
Repeat accuracy± 2.5 %
Off-state current≤ 0.01 mA
Output frequencyStandard: 80 … 800 Hz , low (adjustable): 40 … 400 Hz
Temperature influence0.17 %/K
Compliance with standards and directives
Standard conformity
StandardsEN IEC 60947-5-2:2020
IEC 60947-5-2:2019
Approvals and certificates
UL approvalcULus Listed, Class 2 Power Source
CCC approvalCCC approval / marking not required for products rated ≤36 V
Ambient conditions
Ambient temperature-25 … 70 °C (-13 … 158 °F)
Storage temperature-40 … 85 °C (-40 … 185 °F)
Shock resistance30 g , 11 ms period
Vibration resistance10 … 55 Hz , Amplitude ± 1 mm
Mechanical specifications
Connection typeM8 x 1 connector , 4-pin
Degree of protectionIP67
Material
HousingPolycarbonate
Transducerepoxy resin/hollow glass sphere mixture; polyurethane foam
Installation positionany position
Mass10 g
Tightening torque, fastening screwsmax. 0.2 Nm